CVE-2026-58115
Full vulnerability record from the local CVENow database.
Description
A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions running Example Image versions with Node-RED installed), SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2) (All versions running Example Image versions with Node-RED installed), SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2) (All versions running Example Image versions with Node-RED installed), SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2) (All versions running Example Image versions with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server. This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges.
View original CVE JSON
{
"id": "CVE-2026-58115",
"sourceIdentifier": "[email protected]",
"published": "2026-08-11T13:19:00.190",
"lastModified": "2026-11-10T12:17:20.330",
"vulnStatus": "Awaiting Analysis",
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions running Example Image versions with Node-RED installed), SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2) (All versions running Example Image versions with Node-RED installed), SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2) (All versions running Example Image versions with Node-RED installed), SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2) (All versions running Example Image versions with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server.\r\nThis could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges."
},
{
"lang": "es",
"value": "Se ha identificado una vulnerabilidad en SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (Todas las versiones anteriores a V4.3.4.1 que ejecutan Industrial OS con Node-RED instalado). Los dispositivos afectados no aplican autenticación en la interfaz HTTP de Node-RED, lo que permite el acceso no autenticado a nodos de programación que son capaces de ejecutar comandos del sistema en el servidor.\nEsto podría permitir a un atacante remoto no autenticado crear flujos maliciosos a través de la interfaz HTTP para ejecutar código arbitrario en el servidor subyacente con privilegios máximos."
}
],
"affected": [
{
"source": "[email protected]",
"affectedData": [
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "V4.3.4-1",
"versionType": "custom",
"status": "affected"
}
]
},
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "*",
"versionType": "custom",
"status": "affected"
}
]
},
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "V4.3.4-1",
"versionType": "custom",
"status": "affected"
}
]
},
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "*",
"versionType": "custom",
"status": "affected"
}
]
},
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "V4.3.4-1",
"versionType": "custom",
"status": "affected"
}
]
},
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "*",
"versionType": "custom",
"status": "affected"
}
]
},
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "V4.3.4-1",
"versionType": "custom",
"status": "affected"
}
]
},
{
"vendor": "Siemens",
"product": "SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2)",
"defaultStatus": "unknown",
"versions": [
{
"version": "0",
"lessThan": "*",
"versionType": "custom",
"status": "affected"
}
]
}
]
}
],
"metrics": {
"cvssMetricV40": [
{
"source": "[email protected]",
"type": "Secondary",
"cvssData": {
"version": "4.0",
"vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
"baseScore": 10.0,
"baseSeverity": "CRITICAL",
"attackVector": "NETWORK",
"attackComplexity": "LOW",
"attackRequirements": "NONE",
"privilegesRequired": "NONE",
"userInteraction": "NONE",
"vulnConfidentialityImpact": "HIGH",
"vulnIntegrityImpact": "HIGH",
"vulnAvailabilityImpact": "HIGH",
"subConfidentialityImpact": "HIGH",
"subIntegrityImpact": "HIGH",
"subAvailabilityImpact": "HIGH",
"exploitMaturity": "NOT_DEFINED",
"confidentialityRequirement": "NOT_DEFINED",
"integrityRequirement": "NOT_DEFINED",
"availabilityRequirement": "NOT_DEFINED",
"modifiedAttackVector": "NOT_DEFINED",
"modifiedAttackComplexity": "NOT_DEFINED",
"modifiedAttackRequirements": "NOT_DEFINED",
"modifiedPrivilegesRequired": "NOT_DEFINED",
"modifiedUserInteraction": "NOT_DEFINED",
"modifiedVulnConfidentialityImpact": "NOT_DEFINED",
"modifiedVulnIntegrityImpact": "NOT_DEFINED",
"modifiedVulnAvailabilityImpact": "NOT_DEFINED",
"modifiedSubConfidentialityImpact": "NOT_DEFINED",
"modifiedSubIntegrityImpact": "NOT_DEFINED",
"modifiedSubAvailabilityImpact": "NOT_DEFINED",
"Safety": "NOT_DEFINED",
"Automatable": "NOT_DEFINED",
"Recovery": "NOT_DEFINED",
"valueDensity": "NOT_DEFINED",
"vulnerabilityResponseEffort": "NOT_DEFINED",
"providerUrgency": "NOT_DEFINED"
}
}
],
"cvssMetricV31": [
{
"source": "[email protected]",
"type": "Secondary",
"cvssData": {
"version": "3.1",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H",
"baseScore": 10.0,
"baseSeverity": "CRITICAL",
"attackVector": "NETWORK",
"attackComplexity": "LOW",
"privilegesRequired": "NONE",
"userInteraction": "NONE",
"scope": "CHANGED",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"availabilityImpact": "HIGH"
},
"exploitabilityScore": 3.9,
"impactScore": 6.0
}
],
"ssvcV203": [
{
"source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"ssvcData": {
"timestamp": "2026-08-12T17:59:33.476267Z",
"id": "CVE-2026-58115",
"options": [
{
"exploitation": "none"
},
{
"automatable": "yes"
},
{
"technicalImpact": "total"
}
],
"role": "CISA Coordinator",
"version": "2.0.3"
}
}
]
},
"weaknesses": [
{
"source": "[email protected]",
"type": "Secondary",
"description": [
{
"lang": "en",
"value": "CWE-306"
}
]
}
],
"references": [
{
"url": "https://cert-portal.siemens.com/productcert/html/ssa-834709.html",
"source": "[email protected]"
}
]
}